PUCT denied internal data center metering. GRUS refiled it the same day.
The order says Senate Bill 6 doesn't require metering your computing load. What to do while the proposal stays alive.
Last week the Public Utility Commission of Texas, or PUCT, denied a petition to meter and regulate the computing load inside data centers. The proposal didn't go away. The same day, the petitioner filed it again as rule text in Project 58317, a docket already open for Senate Bill 6 work, where GRUS filed its July justification. If you run a facility in Texas, you'll want to read that filing.
The petitioner is Green Recursive Utility Service LLC, or GRUS. It says the new filing removed nothing of substance. If that holds, the September version is still on the table: electrical submeters on computing equipment, power and temperature data from your servers and racks, workload and cooling classifications, retained records, independent verification, reporting, and water measurement for evaporative cooling.
Why the commission said no
Senate Bill 6 doesn't expressly or implicitly require metering and regulation of computational efficiency, or of what GRUS calls transport-layer consumption (the computing equipment's demand, split out from the rest of the facility). And opening that proceeding would "redirect staff resources away from these essential rulemaking projects" the commission already has under way.
The vote came on the consent agenda, with no debate on the merits. The written order contains the commission's reasoning.
Commission staff went further in a September 25 memo. Staff said the original version would write a proprietary standard into regulation, and that the revision grew into a reporting regime reaching into other agencies' authority. Staff also flagged the timing.
The comments deadline was September 11, and GRUS filed a 62-page revision on September 10. Staff called the new rule language entirely different and said other commenters hadn't had a chance to review it. GRUS's own correction log cut its heat comparison for a 150-kilowatt rack from about 50 residential furnaces to about five or six, and staff listed overstated thermal calculations among its reasons for recommending denial.
GRUS answered on September 29. It said the goal hadn't changed, and that the revised approach needs no proprietary GRUS meter, no exclusive vendor and no replacement of the utility's billing meter.
JD Key's position
Metering what a data center draws and charging it for what it uses is electricity regulation, and every other customer gets the same treatment. GRUS' requests, whether the regulatory capture version or the September revision, went far past that to require a verified picture of what happens inside the building. How efficiently your servers do their work is your business. You pay the power bill, and market forces have pushed efficiency in other industries for generations. They'll keep doing it here.
What to do this week
Start with GRUS's October 1 request in Project 58317, laid next to the September standard. GRUS says it removed nothing of substance, and a section-by-section comparison will show whether that holds.
There's no comment date in what I've seen for this filing. The Project 58317 filing list is where one would show up, along with any notice the commission posts, so look there before you assume you have time.
The cost test is your own site. Which circuits would need submeters? What do your servers and racks already report? If you run evaporative cooling, what water records do you keep? Those answers tell you what verified reporting would cost to produce.
If you decide to comment, the order already gives you the frame: Senate Bill 6 doesn't require this, and the commission's staff time belongs on the rulemakings the law does require. Staff cited overstated thermal calculations among its reasons to recommend denial, so any numbers you file should be measured, not estimated. Anything filed at the PUCT is public, so decide what you're willing to disclose before you file it.
The last revision, all 62 pages, landed the day before comments were due. If a deadline gets set, I'd recheck the docket the day before and the day of.
Reply if you want help monitoring or responding to critical issues like this.
Source citations
From "Kudos to Texas's Utility Commission for Staying Within its Authority," Hyperscale News, October 5, 2026 (https://hyperscalenews.com/articles/puct-computational-load-metering-petition-denied). Document identifiers cited there:
- October 1 PUCT open meeting, full recording: https://www.youtube.com/watch?v=BCaJLJHEnAo
- Project 60084, item 85: signed denial order
- Project 58317, item 20: GRUS's July 26 justification
- Control 60058, item 1: July 30 petition, sections III, VIII and IX
- Project 60084, item 77: revised measurement standard, sections IV.G and V.D
- Project 60084, item 84: GRUS's September 29 response
- Project 60084, item 83: staff memorandum
- Project 58317, item 96: GRUS's October 1 rule-adoption request